Characterizing HV XLPE cables by electrical, chemical and microstructural measurements on cable peeling: Effects of surface roughness, thermal treatment and peeling location

Dissado, L. A., Fothergill, J., Seeley, A. , Stevens, G. C., Markey, L., Laurent, C., Teyssedre, G., Nilsson, U. H., Platbrood, G. & Montanari, G. C. (2000). Characterizing HV XLPE cables by electrical, chemical and microstructural measurements on cable peeling: Effects of surface roughness, thermal treatment and peeling location. Electrical Insulation and Dielectric Phenomena, 2000, Annual Report, 1, pp. 136-140. doi: 10.1109/ceidp.2000.885246

Abstract

Characterization of the electrical, chemical, and microstructural properties of high voltage cables was the first step of the European project “ARTEMIS”, which has the aim of investigating degradation processes and constructing aging models for the diagnosis of cross-linked polyethylene (XLPE) cables. Cables produced by two different manufacturers were subjected to a large number of electrical, microstructural, and chemical characterizations, using cable peelings, instead of lengths of whole cables, as specimens for the measurements. Here the effect of surface deformation and roughness due to peeling and the relevance and significance of thermal pre-treatment prior to electrical and other measurements is discussed. Special emphasis is put on space charge, conduction current and luminescence measurements. We also consider the dependence of these properties on the spatial position of the specimen within the cable. It is shown that even though the two faces of the cable peel specimens have different roughness, the low-field electrical properties seem quite insensitive to surface roughness, while significant differences are detectable at high fields. Thermal pre-treatment is required to stabilize the insulating material to enable us to obtain reproducible results and reliable inter-comparisons throughout the whole project. The spatial position of the specimens along the cable radius can also have a non-negligible influence on the measured properties, due to differential microstructure and chemical composition.

Publication Type: Article
Additional Information: © 2000 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
Subjects: T Technology > TA Engineering (General). Civil engineering (General)
Departments: Presidents's Portfolio
School of Science & Technology > Engineering
SWORD Depositor:
[thumbnail of Characterizing HV XLPE cables by electrical, chemical and microstructural measurements on cable peeling effects of surface roughness, thermal treatment and peeling location.pdf]
Preview
PDF
Download (475kB) | Preview

Export

Add to AnyAdd to TwitterAdd to FacebookAdd to LinkedinAdd to PinterestAdd to Email

Downloads

Downloads per month over past year

View more statistics

Actions (login required)

Admin Login Admin Login